Olivers Yard Data Centre

London, UK

Project outline

Design of 10,000m² data centre and ancillary offices, security room, entrance and plant areas.

Contract value

£30,000,000

Key features

  • Two HV feeds to give 12 MVA
  • 10 No 800kVA UPS systems
  • 12MW of standby generation
  • Electrical systems arranged on n + 1 basis to give system resilience at each stage
  • 32 175kVA PDU's with static transfer switches
  • Duplicate power feeds to data cabinets
  • 4 No 2.4MW centrifugal chillers and associated dry air coolers
  • Variable volume pumping
  • 120 No 60KW down flow computer room cooling units
  • Mechanical systems arranged on n + 1 basis
  • Positive pressure to data rooms
  • Mechanical systems design to meet 500W/m² data load
  • FM200 fire suppression system
  • Leak detection systems
  • Stand alone control systems
  • Data and power distribution
  • Design arranged for stage completion
  • Conversion of existing building
  • Tight planning requirements on noise emission
  • New generator hall located on roof with floating structure to prevent vibration into data centre
  • High acoustic requirement for generator hall due to adjacent residences
  • New roof plant areas for dry air coolers